PQ5K

General Purposed PQ Monitoring Combined with 4 Quadrant Energy Metering!

The PQ5K is a cost effective monitoring solution that combines general purpose PQ detection (with waveform recording) and 4 quadrant energy monitoring in one instrument. Wide-ranging applications include utility, facility, manufacturing, petro chemical, mission critical and more. The PQ5K is housed in a DIN mounted enclosure with an option for a high resolution, color TFT display. The PQ5K is fully compliant with IEC 61000-4-30 Edition 3 Class A for trustworthy PQ measurements. It can detect and record waveforms for sags/dips, swells, interruptions, as well as recording flicker, harmonics and more, all in parallel with complete energy metering capabilities. Digital I/O provides the ability to read alarms and provide state/condition based monitoring and alarming. IEC 61850, Modbus and Profinet are available for remote communications with 3rd party SCADA and other monitoring systems.

Mobirise

Features

• DIN mounted PQ & Energy monitoring
• IEC 61000-4-30 Class A Edition 3 compliant. Certificate of Conformity from an independent laboratory
• PQDIF, Modbus, IEC 61850, Profinet communications
• Web server for real time meters, setup, reporting
• Enhanced security: Roles Based Access Control (RBAC), https, client white list, security log
• State & condition based monitoring & alarming. Temperature & fault current monitoring
• PQView DE, PQView compatible

Voltage
• Channels: (4) AC
• Nominal Voltage: 57.7 … 400 VLN, 100 … 693 VLL
• Overload capacity: 520 VLN, 900 VLL (permanent)
• Nominal frequency: 42 … 50 … 58 Hz, 50.5 … 60 … 69.5 Hz

Current
• Channels: (4) AC
• Nominal Current: 1 … 5 A (max. 7.5 A)
• Overload capacity: 10 A (permanent), 100 A, 5×1 s, interval 300 s

Sampling rate: 18 kHz

• Single phase
• Split phase
• 3 or 4-wire balanced load
• 3-wire balanced load [2U, 1I]
• 3-wire unbalanced load, Aron connection
• 3 or 4-wire unbalanced load
• 4-wire unbalanced load, Open-Y

DIGITAL INPUTS PASSIVE (standard)
• Nominal voltage: 12/24 V DC (30 V max.)

DIGITAL INPUTS ACTIVE (optional)
• Open circuit voltage: ≤ 15 V

RELAYS (optional)
• Contacts: Changeover contact
• Load capacity: 250 V AC, 2 A, 500 VA; 30 V DC, 2 A, 60 W

DIGITAL OUTPUTS 2 (standard)
• Nominal voltage: 12/24 V DC (30 V max.)

ANALOG OUTPUTS (optional)
• Linearization: Linear, kinked
• Range: ± 20 mA (24 mA max.), bipolar
• Accuracy: ± 0.2 % von 20 mA
• Burden: ≤ 500 Ω (max. 10 V/20 mA)

FAULT CURRENT MONITORING For grounded systems (optional)
• Number of meas. channels: 2 (2 measurement ranges each)
• Measurement range :1 (1A) Earth current measurement
• Measuring transformer: 1/1 up to 1/1000 A
• Alarm limit: 30 mA up to 1000 A
• Measurement range: 2 (2mA) RCM with connection monitoring
• Measuring transformer: Residual current transformer 500/1 up to 1000/1 A
• Alarm limit: 30 mA up to 1 A

TEMPERATURE INPUTS (optional)
• Number of channels: 2
• Measurement sensor: Pt100 / PTC; 2-wire

INSTRUMENT POWER
• Standard nominal voltage: 100…230 V AC, 130…230 V DC
• Optional nominal voltage: 24 … 48 V DC
• Consumption: ≤ 27 VA, ≤ 12 W

ENVIRONMENTAL CONDITIONS, GENERAL INFORMATION
• Operating temperature without UPS: –10 to +55 °C
• Operating temperature with UPS: 0 to +35 °C
• Storage temperature: –25 to +70 °C
• Temperature influence: 0.5 x basic uncertainty per 10 K
• Long-term drift: 0.5 x basic uncertainty per year
• Others: Application group II (IEC/EN 60 688)
• Relative air humidity: <95 % without condensation
• Operating altitude: ≤2000 m above NN
• Only to be used in buildings!

MECHANICAL PROPERTIES
• Housing material Polycarbonate (Makrolon)
• Flammability class: V-0 according UL94, self-extinguishing, not dripping, free of halogen
• Weight 800 g

SAFETY
• Current inputs are galvanically isolated from each other.
• Protection class II (protective insulation, voltage inputs via protective impedance)
• Pollution degree 2
• Protection: IP54 (front), IP30 (housing), IP20 (terminals)
• Measurement category U: 600 V CAT III, I: 300 V CAT III

ETHERNET (standard)
• 100Base TX; RJ45 socket
• Mode: 10/100 MBit/s, full/half duplex, auto-negotiation
• Protocols: Modbus/TCP, http, NTP (time synchronization)

IEC61850 (optional)
• Ethernet 100BaseTX, RJ45 sockets, 2 ports
• Mode: 10/100 Mbit/s, full/half duplex, auto-negotiation. Protocol: IEC61850, NTP

PROFINET IO (optional)
• Conformance class: CC-B
• 100BaseTX, RJ45-Buchsen, 2 ports
• Mode: 10/100 Mbit/s, full/half duplex, auto-negotiation
• Protocol: PROFINET, LLDP, SNMP

MODBUS/RTU (optional)
• RS-485, max. 1200 m (4000 ft)
• Baud rate: 9.6 to 115.2 kBaud

TIME REFERENCE Internal clock
• Clock accuracy: ± 2 minutes/month (15 to 30°C)
• Synchronization via NTP server or GPS

• Voltage, current: ±0.1 %
• Power: ±0.2 %
• Power factor: ±0.1°
• Frequency: ±0.01 Hz
• Imbalance: U, I ±0.5 %
• Harmonic: ±0.5 %
• THD: V, I ±0.5 %
• Active energy: Class 0.5S (IEC/EN 62 053-22)
• Reactive energy: Class 0.5S (IEC/EN 62 053-24)