>> Permanent Power Quality Meter

Encore 61000

Download
> Specification
> Module Options
> Current Probe Options
> IEC61000-4-30 Class A

kamagra kopen lovegra bestellen viagra pil cialis prijs kamagra pil viagra vrouwen cialis goedkoop cialis kopen viagra bestellen levitra kopen lovegra kopen cialis kopen levitra generiek cialis 20 mg kamagra belgie viagra prijs levitra prijs

 

Voltage

  • Channels: (4) differential inputs, AC/DC
  • Sampling: 512 samples/cycle, 16bit A/D, synchronous sampling
  • Range: 1-600 Vrms, +/- 1000VPK, Frequency: 16/20Hz, 50Hz, 60Hz
  • Full Scale Accuracy: 0-600V 0.1% reading +/- 0.05% full scale, 7KHz bandwidth for low/medium
  • Input impedance: 10MΩ to ground
  • Choice of connections: Screw terminals (61MVS), safety connectors (61MVB), D connector (61MZP) for use with (optional) remote pod with screw terminals. Choose one

Current

  • Channels: (4) differential inputs, AC/DC
  • Sampling 512 samples/cycle, 16 bit A/D.
  • Range: Full scale current = 1.5Vrms, crest factor of 3
  • Accuracy: 0.1% reading +/- 0.05% full scale, 3KHz bandwidth for low/ medium freq. transients. Does not include CT.
  • Choice of connections: Screw terminals (61MAS5,1), TR connectors (61MAC), D connector (61MZP) for use with (optional) remote 5A or 1A pod. Choose one

Digital Input

  • 61MDIN: Range: 0 — 135VAC/DC,
  • 1KHZ sampling, Edge or level triggered
  • Logic programmed by user (active high or active low)
  • Time stamped to the millisecond
  • Screw terminals

Memory

  • 1GB internal flash

Monitoring Compliance

  • IEC61000-4-30 Class A, IEC61000-4-7, IEC61000-4-15
  • EN50160, NVE, IEEE1159, IEEE1453, IEEE519, IEEE1459

Communications

  • Standard: RJ45 TCP/IP Ethernet, RS232/RS485
  • Optional: GSM/GPRS modem, analog modem
  • Protocols: XML, Modbus TCP/RTU
  • Time synchronization: NTP, optional internal GPS

Instrument Power

  • Standard: 90 to 250V AC 50/60Hz, 105 to 125VDC
  • Optional: 90 to 250V AC/DC, 50/60Hz
  • Screw terminals
  • 15 minute internal UPS (specified with display & 4 modules)
  • Battery is replaceable in the field

Available Enclosures

  • Panel Mount, 186mm x 186mm cutout
  • 61SGD: with 1/4 VGA color touch display, 12 languages
  • 61SG: without display
  • 61RMTSG: rack mount

Environmental

  • Operating temperature: -10 to 60°C
  • Humidity: 10 to 95%, non-condensing, Indoor use only

Safety and Compliance
CE, ISO9001

Back to Top

 