>> Permanent Power Quality Meter

Encore 61000

Download
> Specification
> Module Options
> Current Probe Options
> IEC61000-4-30 Class A

 

Voltage

  • Channels: (4) differential inputs, AC/DC
  • Sampling: 512 samples/cycle, 16bit A/D, synchronous sampling
  • Range: 1-600 Vrms, +/- 1000VPK, Frequency: 16/20Hz, 50Hz, 60Hz
  • Full Scale Accuracy: 0-600V 0.1% reading +/- 0.05% full scale, 7KHz bandwidth for low/medium
  • Input impedance: 10MΩ to ground
  • Choice of connections: Screw terminals (61MVS), safety connectors (61MVB), D connector (61MZP) for use with (optional) remote pod with screw terminals. Choose one

Current

  • Channels: (4) differential inputs, AC/DC
  • Sampling 512 samples/cycle, 16 bit A/D.
  • Range: Full scale current = 1.5Vrms, crest factor of 3
  • Accuracy: 0.1% reading +/- 0.05% full scale, 3KHz bandwidth for low/ medium freq. transients. Does not include CT.
  • Choice of connections: Screw terminals (61MAS5,1), TR connectors (61MAC), D connector (61MZP) for use with (optional) remote 5A or 1A pod. Choose one

Digital Input

  • 61MDIN: Range: 0 — 135VAC/DC,
  • 1KHZ sampling, Edge or level triggered
  • Logic programmed by user (active high or active low)
  • Time stamped to the millisecond
  • Screw terminals

Memory

  • 1GB internal flash

Monitoring Compliance

  • IEC61000-4-30 Class A, IEC61000-4-7, IEC61000-4-15
  • EN50160, NVE, IEEE1159, IEEE1453, IEEE519, IEEE1459

Communications

  • Standard: RJ45 TCP/IP Ethernet, RS232/RS485
  • Optional: GSM/GPRS modem, analog modem
  • Protocols: XML, Modbus TCP/RTU
  • Time synchronization: NTP, optional internal GPS

Instrument Power

  • Standard: 90 to 250V AC 50/60Hz
  • Optional: 90 to 250V AC/DC, 50/60Hz
  • Screw terminals
  • 15 minute internal UPS (specified with display & 4 modules)
  • Battery is replaceable in the field

Available Enclosures

  • Panel Mount, 186mm x 186mm cutout
  • 61SGD: with 1/4 VGA color touch display, 12 languages
  • 61SG: without display
  • 61RMTSG: rack mount

Environmental

  • Operating temperature: -10 to 60°C
  • Humidity: 10 to 95%, non-condensing, Indoor use only

Safety and Compliance
CE, ISO9001

Back to Top