Power Master® 3 Series

The PowerMaster® 3 Series is an ultra-compact field instrument with a true 3-phase analyzing reference standard that performs various metering site accuracy tests.

Customer load Meter Testing, CT/PT ratio testing, CT/PT burden measurement, meter register/demand testing, and wiring verification are all easily performed with this extremely portable, hand-held 3-phase power analyzer.

In addition, with the new Model 335, phantom load meter testing and CT burden added testing are available to complete your field-testing needs. With many advanced features, this new pint-sized 3-phase power analyzer is revolutionizing field testing as we know it.

Features

  • Customer Load Metering Site Testing
  • Phantom Load Metering Site Testing (with Model 335 accessory)
  • True 3 Phase Reference Standard
  • 0.05% Accuracy Class
  • Vector Diagrams
  • Waveforms
  • Harmonics Analysis to the 50th
  • Customer Load Meter Testing
  • Demand/Register Testing
  • CT and PT Ratio Testing
  • CT Burden Added Testing (with Model 335 accessory)
  • CT and PT Burden Measurement
  • CAT IV 600V Rated
  • Compact Handheld Design – Only 3.5 lbs (1.6 kg)

Specifications

Direct Inputs

AC Current:

  • 3 Inputs, 100mA to 20A RMS (3302 Only)
  • 4mm Locking Banana Plugs
  • AC Voltage:

  • 3 Inputs, 46 to 600V RMS
  • 4mm Banana Plugs
  • Aux. Power:

  • 1 Input, 120 to 240 VAC
  • Probe Inputs

    Two Sets of Three Inputs
    Resolution and Range Determined by Probe
    All Probes are Calibrated Independently of 3 Series

     

    Measurements

    Energy:
    Wh, VARh, VAh

  • 0.05% Accuracy (direct current channels)
  • 0.10% Accuracy (probe channels)
  • Power:

  • 0.05% Accuracy (direct current channels)
  • 0.10% Accuracy (probe channels)
  • Power Factor: -1.00 to 1.00
    Harmonics: Up to 20th harmonic

     

     

    System Connectivity

    Pulse Inputs: 2 (meter pulse input, standard input)
    Pulse Outputs: 1 (standard output)
    USB to PC Port: 1 (connectivity to PC)
    USB Ports: 2 (peripheral devices)
    Ethernet Port: 1
    RS232 Port: 1 (legacy devices)

     

    Other

    Display Resolution: 640 x 480, full color transmissive VGA, LED backlit
    Display Size: 5.7 inches
    Operating Temperature: -20°C to 50°C (-4°F to 122°F)
    Storage Temperature: -30°C to 60°C (-22°F to 140°F)
    Humidity: 0 to 95% non-condensing
    Internal Battery: 11.1V Li-Ion Rechargeable, 2600 mAh
    Dimensions:
    11.6” x 6.2” x 2.0” (295mm x 157mm x 51mm)
    Weight: 3.5 lbs (1.6 kg) Not Including Cables
    Warranty: 1 Year

    *All information subject to change
    *See product manual for detailed specs

    IEC Specifications *Subject to change

    General

    Auxiliary Power Voltage Input: 1 Input, 100 to 240 VAC
    Internal Battery: 11.1V Li-Ion Rechargeable, 2600 mAh
    Auxiliary Power Frequency: 50-60Hz
    Power Consumption: 20W
    Dimensions:W 295mm x H 157mm x L 51mm
    Weight: 1.6 kg Not Including Cables
    Display Resolution: 640 x 480, full color
    Display Size: 5.7 inches
    Operating Temperature: -20°C to 50°C (-4°F to 122°F)
    Storage Temperature: -30°C to 60°C (-22°F to 140°F)
    Humidity: 0 to 95% non-condensing

    Safety

    Safety Certification: IEC 61010-1:2010
    Measurement Category: 600V CAT IV
    Degree of Protection: IP-40

     

    Voltage and Current Measurements

    Inputs Range Accuracy
    Voltage 46-600V 0.05%
    5-46V 0.3%
    20mV-5V 0.5%
    Current Direct 100mA-20A 0.05%
    1mA-100mA 0.1%
    Probe Channel 50mV-3.2V 0.1% (+/- Probe Error)

    Power and Energy Measurements

    Reactive (Q)

    Active (P), Apparent(S)
    Direct (A,B,C) 100mA-20A 0.05%
      1mA-100mA 0.1% (Relative to full scale range)
    Temperature Coefficient -20 – +50 deg C < 0.005%
    Frequency 45-65Hz 0.01Hz
    Phase Angle 0.00 – 359.99 deg 0.01 deg
    Power Factor -1.000 to +1.000 0.001
     
    CT Burden
    Current Direct Voltage Accuracy
    0.1A – 20A 0.1V – 5V 0.05%
    0.1A 0.02V – 0.1V 0.5% relative to full scale range
    PT Burden
    Voltage Current Accuracy
    46V – 600V 0.001A- 0.1A 0.2% of full scale range
    Pulse Input/Output
    Output Output Pusle Length Max Output Frequency Input Max Input Frequency
    5V 330ns active low 1’000’000 imp/s 4V – 12V 2MHz

     

     